Add to Cart
140CPU65160 PLC New IN Box by SCHNEIDER ELECTRIC MODICON 140-CPU-651-60
Quick Details:
SCHNEIDER ELECTRIC
MODICON
140CPU65160
UNITY PROCESSOR
QUANTUM
1024KB
266MHZ
One Year warrabty
SPECIFICATION
Manufacturer | Schneider Electric |
Series | Modicon Quantum |
Electrical connection | 1 female connector, connector type: SUB-D 9 for connecting to the Modbus Plus |
| network |
| 1 connector, connector type: RJ45 for connecting Modbus bus |
| 1 connector, connector type: RJ45 for connecting Ethernet network |
| 1 connector, connector type: MT-RJ (fiber optic) for interconnecting primary and |
| secondary PLCs (hot standby architecture) |
Product or component | Unity processor |
Clock frequency | 266 MHz |
Number of slots | 10 |
| 16 |
| 2 |
| 4 |
| 6 |
Number of racks | 2 - local rack(s) |
Number of distributed I/O station | 63 station(s) - 1 rack(s) - 3 distributed network(s) |
Number of remote I/O station | 31 - 2 remote rack(s) |
Discrete I/O number | 8000 inputs, 8000 outputs - distributed - per network |
| 31744 inputs, 31744 outputs - remote |
| Unlimited (26 slots max) - local |
Analogue I/O number | Unlimited (26 slots max) - local |
| 500 inputs, 500 outputs - distributed - per network |
| 1984 inputs,1984 outputs - remote |
Application specific I/O | Accurate time stamping |
| Counter |
| High-speed interrupt inputs |
| Serial link |
Number of optional modules | 6 (Ethernet, Modbus, Modbus Plus, Profibus DP, Sy/Max) |
Maximum number of connections | Unlimited (AS-Interface) - local |
| 6 (Profibus DP) - local |
| 6 (Modbus Plus) - local |
| 6 (Ethernet TCP/IP) - local |
| 4 (AS-Interface) - remote |
| 2 (AS-Interface) - distributed |
| 1 (USB) |
| 1 (Modbus) - RS232/485 Modbus/ASCII |
Integrated connection type | 1 Ethernet TCP/IP |
| 1 Modbus |
| 1 Modbus Plus |
| 1 USB |
Checks | Process control |
Memory description | Internal RAM 1024 kB |
| Expandable 8 MB - file storage with PCMCIA card |
| Expandable 7168 kB - program with PCMCIA card |
Switch function | Key switch memory port on/off |
Application structure | 4 auxiliary tasks |
| 32 timer interrupt tasks |
| 128 interrupt tasks |
| 128 I/O interrupt tasks |
| 1 periodic fast task |
| 1 cyclic/periodic master task |
Execution time per instruction | 0.4...0.5 µs floating points |
| 0.0525...0.075 µs Boolean |
| 0.045...0.06 µs on word |
| 0.045...0.06 µs on fixed-point arithmetic |
Execution time for 1 K instruction | 10.28 100 % Boolean |
| 10.07 65 % Boolean and 35 % numerical |
System overhead | 1 ms - master task |
| 0.2 ms - fast task |
Bus current requirement | 2760 mA |
Local signalling | 1 LED red for Ethernet collision |
| 1 LED green for Ethernet activity (COM) |